Rated voltage 0.6/1kV (Um=1.2kV) copper conductor plastic insulated (low smoke, halogen-free) prefabricated branch cable
Belongs to category:
Detailed content
Product Standard
This product is manufactured according to JB/T 10636-2006 "Rated voltage 0.6/1kV (Um=1.2kV) copper core plastic insulated prefabricated branch cable" and other standards, and can also be produced according to IEC, British, German and American standards as required by the user.
Application Scope
This product can be widely used in power distribution systems of residential buildings, office buildings, hotels, hospitals, shopping malls, factories, etc. The main cable conductor has no joints, the branch cable conductor joint structure is reasonable, the contact resistance is very small, and it is not affected by thermal expansion and contraction. It also has excellent earthquake resistance, good airtightness and waterproofness, can supply power normally in humid environments, and can also be laid outdoors and underground. It occupies a small building area, which is conducive to the effective use of the building area, and is easy to install.
Usage Characteristics
Rated voltage U0/U is 0.6/1KV
Maximum allowable long-term operating temperature of cable conductor: 90℃ for cables with cross-linked polyethylene insulation;
During short circuit (maximum duration not exceeding 5s), the maximum temperature of the cable conductor shall not exceed 250℃;
Maximum allowable long-term operating temperature of cable conductor: 70℃ for cables with polyvinyl chloride insulation;
During short circuit (maximum duration not exceeding 5s), the maximum temperature of the cable conductor shall not exceed 160℃.
The ambient temperature during cable laying should not be lower than 0℃
The bending radius of the cable shall not be less than 20 times the outer diameter of the cable
Cable Model and Name
Model Name
FZ-WDZC-YJY Copper core cross-linked polyethylene insulated low-smoke halogen-free polyolefin sheathed flame-retardant prefabricated branch cable
FZ-WDZCN-YJY Copper core cross-linked polyethylene insulated low-smoke halogen-free polyolefin sheathed fire-resistant prefabricated branch cable
Note: N can be replaced by A, B, and C, respectively representing flame-retardant A-grade, flame-retardant B-grade, and flame-retardant C-grade
Production Range
Table 1
Core Number Main Cable Branch Cable
1 16-630 4-240
2-5 16-50 4-35
Table 2
Phase Wire 16 25 35
Neutral Wire 10-16 16-25 16-35
Ground Wire 10-16 16-25 16-35
Fire-resistant branch cables shall meet the requirements of Table 3
Table 3
Core Number Main Cable Branch Cable
1 16-120 6-70
Note: The cross-sectional area of the branch cable is configured according to the user's requirements, but the cross-sectional area of the branch cable shall not be larger than that of the main cable.
Keywords: Rated voltage 0.6/1kV (Um=1.2kV) copper conductor plastic insulated (low smoke, halogen-free) prefabricated branch cable