6kV~35kV copper-core, aluminum-core, cross-linked polyethylene insulated flame-retardant cables

• Rated voltage at power frequency U0/U is 3.6/6kV~26/35kV. • Maximum allowable operating temperature of cable conductor: 90℃. • During short circuit (maximum duration not exceeding 5s), the maximum temperature of the cable conductor does not exceed 250℃. • Ambient temperature during cable laying should not be lower than 0℃. • Cable bending radius: Not less than 15 times the outer diameter of the cable for three-core cables; not less than 20 times the outer diameter of the cable for single-core cables.

Detailed content

Product Standard

This product is manufactured according to GB/T12706-2008 "Insulated and sheathed cables and accessories with rated voltage from 1kV to 35kV Part 2: Cables with rated voltage 6kV and 30kV Part 3: Cables with rated voltage 35kV", and can also be manufactured according to IEC, British, German and American standards as required by the user.

 

Scope of Application

This product is suitable for fixed installation in distribution networks or industrial equipment with rated voltage of 35kV and below.

 

Usage Characteristics

• Rated voltage U0/U at power frequency: 3.6/6kV~26/35kV.
• Maximum allowable operating temperature of cable conductor: 90℃.
• Maximum temperature of cable conductor during short circuit (not exceeding 5s): 250℃.
• Ambient temperature during cable laying should not be lower than 0℃.
• Cable bending radius: Not less than 15 times the outer diameter for three-core cables; not less than 20 times the outer diameter for single-core cables.

 

Selection of Cable Rated Voltage

• The rated voltage of the cable should be suitable for the operating conditions of the cable system, expressed as U0/U (Um) kV.
U0 - Rated power frequency voltage between conductor and ground or metal shield used in cable design;
U - Rated power frequency voltage between conductors used in cable design;
Um - Maximum value of the "maximum system voltage" that the equipment can withstand.
• The recommended U0 values for three-phase system cables are shown in the table below:
U kV Um kV U0 * kV
A and B Class Systems C Class Systems
6 7.2 3.6 6
10 12 6 8.7
15 17.5 8.7 12
20 24 12 18
30 36 18 —
35 40.5 21 26
A Class System - In this type of system, when any phase conductor comes into contact with the ground or grounding conductor, it can be separated from the system within 1 minute.
B Class System - This type of system only includes the condition of short-term operation of single-phase ground fault, and the ground fault time should not exceed 1 hour, but in any case, the maximum is not more than 8 hours per year, and the total duration of ground fault should not exceed 125 hours;
C Class System - Systems that do not belong to A or B class.

 

Cable Model

Model Name
ZA-YJV Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed flame-retardant A class cable
ZB-YJV Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed flame-retardant B class cable
ZC-YJV Copper core cross-linked polyethylene insulated polyvinyl chloride sheathed flame-retardant C class cable
ZA-YJLV Aluminum core cross-linked polyethylene insulated polyvinyl chloride sheathed flame-retardant A class cable
ZB-YJLV Aluminum core cross-linked polyethylene insulated polyvinyl chloride sheathed flame-retardant B class cable
ZC-YJLV Aluminum core cross-linked polyethylene insulated polyvinyl chloride sheathed flame-retardant C class cable
ZA-YJY Copper core cross-linked polyethylene insulated polyethylene sheathed flame-retardant A class cable
ZB-YJY Copper core cross-linked polyethylene insulated polyethylene sheathed flame-retardant B class cable
ZC-YJY Copper core cross-linked polyethylene insulated polyethylene sheathed flame-retardant C class cable
ZA-YJLY Aluminum core cross-linked polyethylene insulated polyethylene sheathed flame-retardant A class cable
ZB-YJLY Aluminum core cross-linked polyethylene insulated polyethylene sheathed flame-retardant B class cable
ZC-YJLY Aluminum core cross-linked polyethylene insulated polyethylene sheathed flame-retardant C class cable
ZA-YJV22 Copper core cross-linked polyethylene insulated steel tape armored polyvinyl chloride sheathed flame-retardant A class cable
ZB-YJV22 Copper core cross-linked polyethylene insulated steel tape armored polyvinyl chloride sheathed flame-retardant B class cable
ZC-YJV22 Copper core cross-linked polyethylene insulated steel tape armored polyvinyl chloride sheathed flame-retardant C class cable
ZA-YJLV22 Aluminum core cross-linked polyethylene insulated steel tape armored polyvinyl chloride sheathed flame-retardant A class cable
ZB-YJLV22 Aluminum core cross-linked polyethylene insulated steel tape armored polyvinyl chloride sheathed flame-retardant B class cable
ZC-YJLV22 Aluminum core cross-linked polyethylene insulated steel tape armored polyvinyl chloride sheathed flame-retardant C class cable
ZA-YJV23 Copper core cross-linked polyethylene insulated steel tape armored polyethylene sheathed flame-retardant A class cable
ZB-YJV23 Copper core cross-linked polyethylene insulated steel tape armored polyethylene sheathed flame-retardant B class cable
ZC-YJV23 Copper core cross-linked polyethylene insulated steel tape armored polyethylene sheathed flame-retardant C class cable
ZA-YJLV23 Aluminum core cross-linked polyethylene insulated steel tape armored polyethylene sheathed flame-retardant A class cable
ZB-YJLV23 Aluminum core cross-linked polyethylene insulated steel tape armored polyethylene sheathed flame-retardant B class cable
ZC-YJLV23 Aluminum-core cross-linked polyethylene insulated steel tape armored polyethylene sheathed flame-retardant Class C cable

 

Production Range

Model Core Number
Nominal Cross Section mm² 2
ZA-YJV 3.6/6KV
ZA-YJLV 3.6/6KV 1 25-630
ZA-YJY 3.6/6KV
ZA-YJLY 3.6/6KV 3 25-630
ZA-YJV22 3.6/6KV
ZA-YJLV22 3.6/6KV 1 25-630
ZA-YJV23 3.6/6KV
ZA-YJLV23 3.6/6KV 3 25-630
ZA-YJV 6/6KV(YJV 6/10KV)
ZA-YJLV 6/6KV(YJLV 6/10KV) 1 25-630
ZA-YJY 6/6KV(YJV 6/10KV)
ZA-YJLY 6/6KV(YJLV 6/10KV) 3 25-630
ZA-YJV22 6/6KV(YJV22 6/10KV)
ZA-YJLV22 6/6KV(YJV22 6/10KV) 1 25-630
ZA-YJV23 6/6KV(YJV23 6/10KV)
ZA-YJLV23 6/6KV(YJV23 6/10KV) 3 25-630
ZA-YJV 8.7/10KV(YJV 8.7/15KV)
ZA-YJLV 8.7/10KV(YJLV 8.7/15KV) 1 25-630
ZA-YJY 8.7/10KV(YJV 8.7/15KV)
ZA-YJLY 8.7/10KV(YJLV 8.7/15KV) 3 25-630
ZA-YJV22 8.7/10KV(YJV22 8.7/15KV)
ZA-YJLV22 8.7/10KV(YJV22 8.7/15KV) 1 25-630
ZA-YJV23 8.7/10KV(YJV23 8.7/15KV)
ZA-YJLV23 8.7/10KV(YJV23 8.7/15KV) 3 25-630
ZA-YJV 12/20KV
ZA-YJLV 12/20KV 1 35-630
ZA-YJY 12/20KV
ZA-YJLY 12/20KV 3 35-630
ZA-YJV22 12/20KV
ZA-YJLV22 12/20KV 1 35-630
ZA-YJV23 12/20KV
ZA-YJLV23 12/20KV 3 35-630
ZA-YJV 18/30KV
ZA-YJLV 18/30KV 1 50-630
ZA-YJY 18/30KV
ZA-YJLY 18/30KV 3 50-500
ZA-YJV22 18/30KV
ZA-YJLV22 18/30KV 1 50-630
ZA-YJV23 18/30KV
ZA-YJLV23 18/30KV 3 50-500
ZA-YJV 26/35KV
ZA-YJLV 26/35KV 1 50-630
ZA-YJY 26/35KV
ZA-YJLY 26/35KV 3 50-500
ZA-YJV22 26/35KV
ZA-YJLV22 26/35KV 1 35-630
ZA-YJV23 26/35KV
ZA-YJLV23 26/35KV 3 50-500


Model Core Number
Nominal Cross Section mm² 2
ZB-YJV 3.6/6KV
ZB-YJLV 3.6/6KV 1 25-630
ZB-YJY 3.6/6KV
ZB-YJLY 3.6/6KV 3 25-630
ZB-YJV22 3.6/6KV
ZB-YJLV22 3.6/6KV 1 25-630
ZB-YJV23 3.6/6KV
ZB-YJLV23 3.6/6KV 3 25-630
ZB-YJV 6/6KV(YJV 6/10KV)
ZB-YJLV 6/6KV(YJLV 6/10KV) 1 25-630
ZB-YJY 6/6KV(YJV 6/10KV)
ZB-YJLY 6/6KV(YJLV 6/10KV) 3 25-630
ZB-YJV22 6/6KV(YJV22 6/10KV)
ZB-YJLV22 6/6KV(YJV22 6/10KV) 1 25-630
ZB-YJV23 6/6KV(YJV23 6/10KV)
ZB-YJLV23 6/6KV(YJV23 6/10KV) 3 25-630
ZB-YJV 8.7/10KV(YJV 8.7/15KV)
ZB-YJLV 8.7/10KV(YJLV 8.7/15KV) 1 25-630
ZB-YJY 8.7/10KV(YJV 8.7/15KV)
ZB-YJLY 8.7/10KV(YJLV 8.7/15KV) 3 25-630
ZB-YJV22 8.7/10KV(YJV22 8.7/15KV)
ZB-YJLV22 8.7/10KV(YJV22 8.7/15KV) 1 25-630
ZB-YJV23 8.7/10KV(YJV23 8.7/15KV)
ZB-YJLV23 8.7/10KV(YJV23 8.7/15KV) 3 25-630
ZB-YJV 12/20KV
ZB-YJLV 12/20KV 1 35-630
ZB-YJY 12/20KV
ZB-YJLY 12/20KV 3 35-630
ZB-YJV22 12/20KV
ZB-YJLV22 12/20KV 1 35-630
ZB-YJV23 12/20KV
ZB-YJLV23 12/20KV 3 35-630
ZB-YJV 18/30KV
ZB-YJLV 18/30KV 1 50-630
ZB-YJY 18/30KV
ZB-YJLY 18/30KV 3 50-500
ZB-YJV22 18/30KV
ZB-YJLV22 18/30KV 1 50-630
ZB-YJV23 18/30KV
ZB-YJLV23 18/30KV 3 50-500
ZB-YJV 26/35KV
ZB-YJLV 26/35KV 1 50-630
ZB-YJY 26/35KV
ZB-YJLY 26/35KV 3 50-500
ZB-YJV22 26/35KV
ZB-YJLV22 26/35KV 1 35-630
ZB-YJV23 26/35KV
ZB-YJLV23 26/35KV 3 50-500

Model Core Number
Nominal Cross Section mm² 2
ZC-YJV 3.6/6KV
ZC-YJLV 3.6/6KV 1 25-630
ZC-YJY 3.6/6KV
ZC-YJLY 3.6/6KV 3 25-630
ZC-YJV22 3.6/6KV
ZC-YJLV22 3.6/6KV 1 25-630
ZC-YJV23 3.6/6KV
ZC-YJLV23 3.6/6KV 3 25-630
ZC-YJV 6/6KV(YJV 6/10KV)
ZC-YJLV 6/6KV(YJLV 6/10KV) 1 25-630
ZC-YJY 6/6KV(YJV 6/10KV)
ZC-YJLY 6/6KV(YJLV 6/10KV) 3 25-630
ZC-YJV22 6/6KV(YJV22 6/10KV)
ZC-YJLV22 6/6KV(YJV22 6/10KV) 1 25-630
ZC-YJV23 6/6KV(YJV23 6/10KV)
ZC-YJLV23 6/6KV(YJV23 6/10KV) 3 25-630
ZC-YJV 8.7/10KV(YJV 8.7/15KV)
ZC-YJLV 8.7/10KV(YJLV 8.7/15KV) 1 25-630
ZC-YJY 8.7/10KV(YJV 8.7/15KV)
ZC-YJLY 8.7/10KV(YJLV 8.7/15KV) 3 25-630
ZC-YJV22 8.7/10KV(YJV22 8.7/15KV)
ZC-YJLV22 8.7/10KV(YJV22 8.7/15KV) 1 25-630
ZC-YJV23 8.7/10KV(YJV23 8.7/15KV)
ZC-YJLV23 8.7/10KV(YJV23 8.7/15KV) 3 25-630
ZC-YJV 12/20KV
ZC-YJLV 12/20KV 1 35-630
ZC-YJY 12/20KV
ZC-YJLY 12/20KV 3 35-630
ZC-YJV22 12/20KV
ZC-YJLV22 12/20KV 1 35-630
ZC-YJV23 12/20KV
ZC-YJLV23 12/20KV 3 35-630
ZC-YJV 18/30KV
ZC-YJLV 18/30KV 1 50-630
ZC-YJY 18/30KV
ZC-YJLY 18/30KV 3 50-500
ZC-YJV22 18/30KV
ZC-YJLV22 18/30KV 1 50-630
ZC-YJV23 18/30KV
ZC-YJLV23 18/30KV 3 50-500
ZC-YJV 26/35KV
ZC-YJLV 26/35KV 1 50-630
ZC-YJY 26/35KV
ZC-YJLY 26/35KV 3 50-500
ZC-YJV22 26/35KV
ZC-YJLV22 26/35KV 1 35-630
ZC-YJV23 26/35KV
ZC-YJLV23 26/35KV 3 50-500

Note: Single-core armored cables are only for DC systems. If used in AC systems, a non-magnetic armor layer or magnetic shielding measures should be used.